KIMI Phone:+86 18059884790      中文版
ABB
Home > ABB
ABB SPAJ141 Combined Overcurrent and Earth-Fault Relay
  • Warehouse: Spot
  • Warranty: 365 days
  • Quality: Original module
  • Condition: New
  • Shipping method: Courier delivery

  • Contact person: LI MING
  • Contact number: +86 18059884790
  • WeChat:18059884790
  • E-mail: plc66@qq.com

Product Description
ABB  ·  SPAJ 140 Series

ABB SPAJ141 Combined Overcurrent and Earth-Fault Relay

The ABB SPAJ141 (SPAJ141C) is a legacy numerical protection relay designed for selective short-circuit and earth-fault protection of medium voltage radial feeders. It is an integrated protection unit combining phase overcurrent and sensitive earth-fault protection, widely used as spare parts for existing distribution automation systems.

image.png

Model: SPAJ141C      Series: SPAJ140C      Status: Obsolete / Legacy Spare      Function: Overcurrent + Earth Fault      Condition: New / Refurbished      Warranty: 12 Months
Request Price & Lead Time      Ask for Test Report

Product Overview

ABB SPAJ141C is a compact numerical protection relay from the SPAJ140C family, dedicated for radial feeder protection in solidly earthed, resistance earthed or impedance earthed medium voltage networks. It integrates multi-stage phase overcurrent protection and sensitive non-directional earth-fault protection, with built-in circuit breaker failure protection. It supports local parameter setting via front panel buttons and display, and remote communication through serial fibre bus for distribution automation systems. This relay has been discontinued by ABB since 2011 and is mainly supplied as spare replacement for running power distribution systems.

Product typeCombined overcurrent & earth-fault protection relay
SystemMedium voltage radial feeder, distribution automation
Auxiliary supply80–265V AC / 18–80V DC
Frequency50 / 60 Hz
CommunicationSerial / fibre-optic bus for remote setting & fault data

Key Features & Functions

Core protection and control functions of the SPAJ141C relay.

01

Multi-stage phase overcurrent protection

Low-set stage with IDMT or definite time; high-set stage with instantaneous or definite time operation for short-circuit protection.

02

Sensitive earth-fault protection

Low-set sensitive earth-fault stage and high-set earth-fault stage, non-directional, suitable for high-resistance earth fault detection.

03

Built-in breaker failure protection

Integrated CBFP function to trigger backup tripping when the circuit breaker fails to open after a trip command.

04

Flexible output matrix

2 heavy-duty trip relays and 4 signal relays, user-configurable matrix to assign start, trip, alarm and CBFP signals freely.

05

Fault recording & local display

Display measured currents, setting parameters and stored fault values locally; fault snapshot for post-fault analysis.

06

Self-supervision & diagnostics

Continuous self-monitoring of internal electronics and microprocessor, alarms for internal hardware or firmware faults.

Application Scenarios

Typical installation and replacement scenarios for SPAJ141C.

MV radial distribution feeders

Primary use for selective short-circuit and earth-fault protection on overhead or cable feeders in medium voltage distribution networks.

Industrial power distribution

Factory internal MV switchgear, auxiliary power protection for plants, refineries and mining facilities with legacy SPAJ relay systems.

Renewable power collection networks

Spares replacement for existing solar or wind farm MV feeder protection panels originally equipped with SPAJ140 series relays.

Substation automation retrofits

Drop-in spare replacement in ABB distribution automation Panorama systems, avoiding full panel upgrade.

Resistance / impedance earthed networks

Suitable for networks with low earth fault current, where sensitive earth fault detection is required.

Circuit breaker failure backup protection

Used where CBFP logic is required within the feeder protection scheme to improve substation reliability.

Frequently Asked Questions

Q. Is ABB SPAJ141C still in production?

No. ABB discontinued SPAJ141C since 2011. It is only available as new old stock or professionally refurbished spare parts for maintenance.

Q. What is the difference between SPAJ141C, SPAJ140C and SPAJ142C?

SPAJ141C provides the sensitive earth-fault input circuit; SPAJ140C is standard version; SPAJ142C has enhanced sensitive earth fault function. They belong to the same SPAJ140C family but cannot be swapped freely without scheme review.

Q. Can I use it for directional earth fault protection?

No. SPAJ141C earth-fault stages are non-directional. For directional earth fault protection, you need other ABB relay models.

Q. How to set parameters for SPAJ141C?

You can set locally via front panel buttons and display, or remotely over serial fibre bus by ABB distribution automation system software.

Q. What is the replacement process for a failed SPAJ141C?

Confirm auxiliary voltage and current transformer ratio, copy the original protection settings, check wiring, download parameters and test trip and alarm functions before commissioning.

Q. Are units tested before shipment?

All stocked SPAJ141C units are fully function tested. We can provide test report upon request, standard warranty is 12 months.

Need SPAJ141C spare for your MV feeder panel?

Send us the relay label photo and network earthing type, we will verify compatibility and quote price and lead time quickly.


Related recommendations