DEIF DU-2/MKIII Generator HMI & Paralleling Control Unit
Product Brief Description
DEIF DU-2/MKIII is an operator display and control unit for DEIF Multi-Line 2 generator control system. It works with PPU, AGC, GPU controllers to realize genset monitoring, synchronisation, load sharing, protection parameter setting and alarm handling. Widely used for marine generator sets, onshore power plants and backup power systems.

Features
- Backlit LCD graphic display, local operation for start/stop, breaker control and parameter modification
- Real-time measurement: voltage, current, frequency, power, power factor, energy and harmonics
- Support generator synchronisation, parallel operation and active/reactive load sharing
- Integrated protection alarm: over/under voltage, over/under frequency, reverse power, overcurrent
- Communication: CAN bus (for DEIF internal bus), RS485 Modbus RTU, optional Ethernet Modbus TCP
- Auxiliary supply: 24VDC, operating temperature -25℃ ~ +70℃
- Panel mounting design, event log and fault history recording function
Application Scenarios
- Marine vessel power station, multiple generator parallel control
- Land-based standby power station, data centre backup genset system
- Oil & gas, mining and industrial self-contained power supply system
- DEIF Multi-Line2 system retrofit, HMI replacement and spare upgrade
- Generator control room local monitoring and manual synchronisation operation
FAQ
Q: What is the difference between DU-2/MKIII and PPU-3?
A: DU-2/MKIII is HMI display panel, it cannot work independently; PPU-3 is the main protection and paralleling controller. DU-2/MKIII connects to PPU-3 via CAN bus for operation and display.
Q: Can DU-2/MKIII control generators alone?
A: No, it is only a man-machine interface. It must be matched with DEIF Multi-Line2 series controllers such as PPU, AGC.
Q: What communication port connects to DEIF main controller?
A: CAN bus is the dedicated internal bus for Multi-Line2; RS485 Modbus is used for SCADA upper computer.
Q: What is the mounting type?
A: Panel cutout mounting, suitable for generator control cabinet door installation.
Q: Is this unit available for spare replacement?
A: It is a mature DEIF Multi-Line2 HMI part. New surplus and refurbished units are supplied for marine and power plant maintenance.