KIMI Phone:+86 18059884790      中文版
HONEYWEL
Honeywell LG1093AA24 / 261A1812P012 UV Flame Sensor
  • Warehouse: Spot
  • Warranty: 365 days
  • Quality: Original module
  • Condition: New
  • Shipping method: Courier delivery

  • Contact person: LI MING
  • Contact number: +86 18059884790
  • WeChat:18059884790
  • E-mail: plc66@qq.com

Product Description

Honeywell LG1093AA24 / 261A1812P012 UV Flame Sensor

Product Brief Description

The Honeywell LG1093AA24 with part suffix 261A1812P012 is a heavy-duty ultraviolet flame sensor equipped with factory integrated shielded cable, designed to pair with Honeywell EG1033 flame amplifier units. It detects ultraviolet radiation emitted by gas and light oil combustion flames. Built with stainless steel housing, wide operating temperature range and IP65 protection, this UV probe delivers stable flame signal transmission under high vibration and thermal radiation conditions, commonly used for gas turbine, boiler and industrial burner management safety systems.

image.png

Product Functions

  • Capture ultraviolet radiation within 250~350nm spectrum generated by natural gas and light oil flames
  • Convert UV flame radiation into analog electrical signal and transmit to matched EG1033 flame amplifier via pre-wired shielded cable
  • Built-in current-limiting resistor protects the sensing tube against electrical surge and transient voltage damage
  • 3/4" NPT mounting thread for direct installation on burner sight ports of gas turbines and industrial boilers
  • High vibration and thermal resistance design for continuous long-term operation inside turbine enclosures and furnace areas
  • Work together with flame amplifier to judge flame presence or loss and trigger safety fuel shutoff interlock protection

Application Scenarios

  • GE heavy-duty gas turbine combustion flame safety monitoring systems
  • Power plant gas-fired boilers, waste heat boilers and industrial furnace burner management
  • Oil & gas refinery process heaters and thermal oxidizer flame safeguard control
  • Onshore and offshore gas turbine generator combustion supervision
  • Spare replacement and retrofit projects for Honeywell LG1093 series UV flame sensors

Frequently Asked Questions

Q: What is LG1093AA24/261A1812P012?
A: It is Honeywell ultraviolet flame sensor with factory cable assembly, matched with EG1033 flame amplifier for gas turbine and boiler flame safety detection.

Q: What amplifier does it require?
A: Must be used with Honeywell EG1033 flame amplifier, one amplifier supports up to two LG1093 UV sensors.

Q: What fuels can it monitor?
A: Optimized for natural gas and light fuel oil; not suitable for heavy oil or coal flame with heavy soot contamination.

Q: What maintenance is needed?
A: Periodically clean the optical window to remove soot and dust; inspect cable insulation and connector tightness on a regular basis.

Q: Does this flame sensor support hot swap?
A: Hot swap is prohibited. Shut down the burner, cut power to flame amplifier and isolate fuel supply before sensor removal and replacement.