KIMI Phone:+86 18059884790      中文版
HONEYWEL
Honeywell FSC 10216/2/1 Product Description
  • Warehouse: Spot
  • Warranty: 365 days
  • Quality: Original module
  • Condition: New
  • Shipping method: Courier delivery

  • Contact person: LI MING
  • Contact number: +86 18059884790
  • WeChat:18059884790
  • E-mail: plc66@qq.com

Product Description

Honeywell FSC 10216/2/1 Product Description

Honeywell FSC 10216/2/1 is a 4-channel fail-safe loop-monitored digital output module for Honeywell Fail Safe Controller (FSC) safety instrumented systems (SIS). It provides 24VDC solid-state outputs to drive safety-related field devices and continuously monitors each field circuit for open or short conditions. This SIL3 certified I/O module ensures outputs de-energize to safe state upon internal or wiring faults, widely deployed for ESD and fire & gas safety systems and stocked as tested spare replacement parts for legacy FSC racks.

image.png

Product Features

  • 4 independent 24VDC solid-state output channels, rated 1A per channel
  • Built-in loop monitoring to detect open circuit, short circuit and wiring faults
  • Fail-safe design; outputs de-energize to predefined safe state during failure
  • SIL3 safety integrity certification with TÜV, CE and UL approvals
  • Integrated short-circuit and overload protection for field loads
  • 3U 4HP rack form factor, hot-swappable inside FSC chassis
  • Comprehensive self-diagnostics with fault reporting to FSC processor
  • Inductive load suppression for solenoid valves and relay loads
  • High EMC immunity for noisy industrial and hazardous area control cabinets

Application Scenarios

  • Emergency Shutdown (ESD) safety systems for oil & gas plants and refineries
  • Fire and Gas (F&G) detection and suppression control panels
  • Power plant boiler and turbine safety interlock protection systems
  • Chemical and petrochemical process safety instrumented systems (SIS)
  • Offshore platform safety shutdown and hazard mitigation control
  • Legacy Honeywell FSC cabinet maintenance, overhaul and spare replacement

FAQ

Q1: What is Honeywell FSC 10216/2/1?
A: It is a 4-channel SIL3 fail-safe digital output I/O module for Honeywell FSC SIS systems, used to control safety solenoids and relays with continuous circuit supervision.

Q2: Is FSC series still in original production?
A: Honeywell has discontinued the FSC platform. Our available units are fully tested spare modules for existing safety system replacement.

Q3: What is the rated output specification?
A: 24VDC solid-state source output, maximum 1A per channel, total module thermal limit 3.6A.

Q4: What does loop monitoring do?
A: It continuously checks field wiring to identify open or short circuit faults, sending diagnostic alarms back to the FSC controller before safety function failure occurs.

Q5: How to confirm compatibility before purchase?
A: Confirm your FSC rack model, firmware revision and slot configuration. Match full part number and safety logic requirements before installation.