KIMI Phone:+86 18059884790      中文版
HONEYWEL
Notifier (Honeywell) HS-NCM-MF High-Speed Multi-Mode
  • Warehouse: Spot
  • Warranty: 365 days
  • Quality: Original module
  • Condition: New
  • Shipping method: Courier delivery

  • Contact person: LI MING
  • Contact number: +86 18059884790
  • WeChat:18059884790
  • E-mail: plc66@qq.com

Product Description

Notifier (Honeywell) HS-NCM-MF High-Speed Multi-Mode Fiber Network Communication Module

Product Description

The HS-NCM-MF is a high-speed network communication module for Notifier Onyx series fire alarm systems, working on High-Speed NOTI•FIRE•NET (HS-NFN). It uses multi-mode fiber to interconnect multiple fire control panels, NCA-2 network annunciators and DVC voice command units into one unified fire alarm network. It supports up to two node addresses, and can also run as a fiber repeater to extend network distance. It is the matching network card for NFS2-3030 fire panel (CPU2-3030D / AMPS-24/E).

image.png

Features

  • Part No: HS-NCM-MF, Brand: Notifier (Honeywell)
  • Medium: Multi-mode fiber, LC fiber connector, 1310nm wavelength
  • Transmission rate: 100Mbps, supports NFPA Style4 (Class B) / Style7 (Class A) redundant ring
  • Fiber specification: 62.5/125μm or 50/125μm multi-mode fiber
  • Optical isolation, anti-EMI, eliminate ground loop interference
  • Supports max 2 node addresses on one module, one card for two panels
  • Built-in network status LEDs, supports online programming and database upload/download
  • Power supply: 24VDC, low power consumption
  • Compatible models: NFS2-3030, NFS2-640, NCA-2, DVC

Applications

  • Campus, high-rise building, industrial park multi-node fire alarm networking
  • NFS2-3030 fire panel fiber network interconnection
  • Long-distance network transmission where twisted-pair cannot reach
  • Substation, data center, hospital fire alarm network retrofit
  • Spare replacement and expansion of existing HS-NFN fiber network

FAQ

Q: What is the difference between HS-NCM-MF and HS-NCM-SF?
A: MF = Multi-mode fiber; SF = Single-mode fiber, for longer distance transmission.

Q: Can it match NFS2-3030?
A: Yes, it is the official fiber network module for NFS2-3030 Onyx system.

Q: Is this module discontinued?
A: Onyx NFS2-3030 series is legacy fire alarm hardware, original production stopped, supplied as surplus, refurbished and tested spare parts only.

Q: Can it work with old low-speed Noti-Fire-Net?
A: No, HS-NCM is only for High-Speed NFN, incompatible with old low-speed NCM network.