YOKOGAWA PK200-A33
Brief Description
PK200-A33 is a Yokogawa PK200 series current-to-pneumatic (I/P) converter. It converts 4-20mA DC electronic control signal into proportional pneumatic pressure output for pneumatic valve actuators, widely used in hybrid DCS and pneumatic valve control loops for process plants.

Product Features & Functions
- Input: 4–20mA DC, standard output 20–100kPa pneumatic signal
- Electronic feedback control, linearity ±0.2% of span, repeatability 0.1% of span
- Built-in stainless steel input and output pressure gauges for local reading
- Low air consumption (max 4 Nl/min) with high air delivery capacity up to 110 Nl/min
- Reverse polarity protection, no damage under current reversal or over-current up to 62mA
- Cast aluminum housing with epoxy coating, suitable for harsh field environments
- Surface or 2-inch pipe mounting, standard 1/4 NPT air connections
Application Scenarios
- Yokogawa CENTUM DCS matching pneumatic control valves
- Oil & gas, petrochemical, chemical and refinery process control loops
- Power plant boiler, water treatment and pulp & paper pneumatic actuator control
- Diaphragm control valves, air cylinder actuators and pneumatic positioners
- Legacy I/P converter replacement and field instrument maintenance
FAQ
Q: What is the main function of PK200-A33?
A: It is an I/P converter, converting 4-20mA electric signal to pneumatic pressure to drive pneumatic control valves.
Q: What is the standard air supply pressure?
A: Standard supply pressure is 140kPa for 20–100kPa output range.
Q: Does it support hazardous area installation?
A: Explosion-proof variants are available; confirm the full model code for approvals before ordering.
Q: Will you test the unit before shipment?
A: Each unit is calibrated and function tested. Calibration report can be provided upon request.